Product Overview
This multifunction intelligent network meter is designed for power monitoring requirements in power systems, industrial and mining enterprises, public facilities, and intelligent buildings. It measures commonly used electrical parameters and displays operating information through a high-brightness LED or optional LCD interface.
The product can replace conventional auxiliary units used with transmitters and is suitable for automatic distribution systems. With RS-485 communication, programmable display settings, simple wiring, and compact installation, it can connect with PLCs, industrial control computers, and monitoring software.
Key Features
- Measures three-phase voltage, current, active power, reactive power, power factor, active energy, reactive energy, and frequency.
- Supports three-phase three-wire and three-phase four-wire network systems.
- RMS measurement with 0.5 class accuracy for voltage and current, and 0.5 class accuracy for active and reactive power.
- Active energy accuracy reaches class 1.0; reactive energy accuracy reaches class 2.0.
- Programmable LED or LCD display supports switching, cycling display, and custom display page selection.
- RS-485 digital communication with MODBUS-RTU protocol supports integration into monitoring and automation systems.
- Optional pulse output, switch input, switch output, and 4-20mA analog output support expanded control and data acquisition needs.
- Wide auxiliary power input and industrial operating temperature range make it suitable for panel and cabinet installation.
Main Technical Specifications
|
Item |
Specification |
|
Product category |
Multifunction intelligent network electrical meter |
|
Network type |
Three-phase three-wire / three-phase four-wire |
|
Voltage rated value |
AC100V / AC400V, specify when ordering |
|
Voltage overload |
1.2 times continuous; 2 times instantaneous |
|
Voltage power consumption |
< 1VA per phase |
|
Voltage input impedance |
>= 500k ohm |
|
Voltage accuracy |
RMS measurement, class 0.5 |
|
Current rated value |
AC5A |
|
Current overload |
1.2 times continuous; 2 times instantaneous |
|
Current power consumption |
< 0.4VA per phase |
|
Current input impedance |
< 2m ohm |
|
Current accuracy |
RMS measurement, class 0.5 |
|
Frequency |
45-65Hz, accuracy 0.1Hz |
|
Power measurement |
Active power and reactive power, class 0.5 |
|
Energy measurement |
Active energy class 1.0; reactive energy class 2.0 |
Power Supply, Output, and Safety
|
Item |
Specification |
|
Auxiliary power supply |
AC / DC 80-265V |
|
Power consumption |
<= 5VA |
|
Digital interface |
RS-485, MODBUS-RTU protocol |
|
Pulse output |
2 energy pulse outputs, optocoupler relay |
|
Switch input |
4 switch inputs, dry contact mode, optional configuration |
|
Switch output |
4 switch outputs, relay output, optional configuration |
|
Analog output |
4 analog outputs, 4-20mA |
|
Operating temperature |
-10°C to +55°C |
|
Storage temperature |
-20°C to +75°C |
|
Withstand voltage |
Input / power supply > 2kV; input / output > 2kV; power supply / output > 1kV |
|
Insulation |
Input, output, and power supply to housing > 50M ohm |
Display and Programmable Functions
- DISP=1 can display three-phase voltage values, with phase voltage or line voltage depending on the wiring system.
- DISP=2 can display three-phase current values.
- DISP=3 can display active power, reactive power, and power factor.
- DISP=4 can display active energy.
- DISP=5 can display reactive energy.
- DISP=6 can display frequency and switch input status.
- Programmable settings include display page, input network, voltage range, current range, CT/PT ratio, communication address, baud rate, and password.
- Display brightness range is adjustable from 1 to 15; energy clearing is supported through the programming menu.
Communication Parameters
|
Item |
Specification |
|
Protocol |
MODBUS-RTU |
|
Physical layer |
RS-485 communication |
|
Address range |
1-247 from programming menu; communication protocol address field supports 1-255 |
|
Baud rate |
4800 / 9600 bps, 9600 default in source description |
|
Communication mode |
Shielded twisted-pair cable recommended |
|
Data frame options |
8 data bits with odd, even, or no parity; 1 stop bit |
|
Function codes shown |
03H read data, 06H write single register, 08H diagnostic, 10H write multiple registers |
|
Response time |
Typical response query time 0.1-0.5s; response interval about 0.2s |
Recommended Applications
This smart electrical meter is suitable for power monitoring and data acquisition in low-voltage distribution and automation systems.
- Power distribution cabinets and switchgear panels
- Industrial and mining enterprise monitoring systems
- Public facility power management
- Smart building electrical monitoring
- Energy management and sub-metering systems
- PLC, industrial PC, and monitoring software networks
- Automatic distribution systems requiring digital measurement and communication
Installation and Ordering Notes
- Confirm the network type before ordering: three-phase three-wire or three-phase four-wire.
- Specify the voltage input range, such as AC100V or AC400V.
- Confirm current input range, CT ratio, and PT ratio according to the actual distribution system.
- Select LED or LCD display mode according to panel design and reading preference.
- Confirm whether RS-485 communication, pulse output, switch input/output, or 4-20mA analog output is required.
- After changing internal parameter settings, make sure external wiring and system parameters match the meter settings to avoid inaccurate measurement.
Request a Quote
Send us your wiring system, voltage input, current input, CT/PT ratio, display type, communication requirement, output configuration, and quantity. Our team can help select a suitable multifunction network meter for accurate power monitoring and smart distribution management.
Hot Tags: power panel meter, China power panel meter manufacturers, suppliers, factory, Amp Meter, Frequency Meter, Harmonic Meter, panel meter, Power Factor Meter, Voltage Current Frequency Combination Meter