Product Overview
The LDX2(CJX2) series three-pole AC contactor is designed for remote making and breaking of circuits, frequent starting of AC motors, and reliable control in electrical panels. It is suitable for AC 50Hz or 60Hz applications with rated operating voltage up to 660V, and the AC-3 motor-control current range covers compact cabinet applications up to 95A at 380V.
When matched with a suitable thermal overload relay, the contactor can form an electromagnetic starter to support motor overload protection. The product family is based on a proven LC1-D style structure, offering compact size, low power consumption, flexible auxiliary contact options, and practical mounting choices for motor control cabinets and automation systems.
Key Features
- Three-pole main contact structure for AC motor control and power switching.
- Designed for remote circuit making, breaking, and frequent motor starting.
- Rated for AC 50/60Hz systems with insulation voltage up to 660V.
- AC-3 motor-control rated current range covers 9A to 95A at 380V.
- Coil voltage options include 36V, 110V, 220V, and 380V AC at 50Hz, with other configurations available by requirement.
- Optional normally open and normally closed auxiliary contacts support control circuit expansion.
- Compact body, light weight, low coil power consumption, and long service life support dense cabinet layouts.
- Supports screw mounting, 35mm rail installation, and selected 75mm rail installation depending on product size.
Main Technical Specifications
|
Item |
Specification |
|
Product series |
LDX2(CJX2) series AC contactor |
|
Pole configuration |
Three-pole main contact design |
|
Application |
Remote switching, frequent motor starting, AC motor control |
|
Rated frequency |
AC 50Hz / 60Hz |
|
Rated insulation voltage |
Up to 660V |
|
Rated operating voltage |
Up to 660V; AC-3 reference at 380V |
|
Rated operating current |
AC-3 up to 95A at 380V |
|
Coil voltage options |
AC 50Hz: 36V, 110V, 220V, 380V and other options by requirement |
|
Coil operating range |
Pick-up at 85%-110% Us; release voltage not higher than 75% Us and not lower than 20% Us |
|
Installation category |
III |
|
Pollution degree |
3 |
|
Standards |
GB14048.4 / IEC947 |
Model and Current Range
|
Model |
AC-3 Rated Current at 380V |
Reference Motor Power at 380V |
|
LDX2-09 |
9A |
4kW |
|
LDX2-12 |
12A |
5.5kW |
|
LDX2-18 |
18A |
7.5kW |
|
LDX2-25 |
25A |
11kW |
|
LDX2-32 |
32A |
15kW |
|
LDX2-40 |
40A |
18.5kW |
|
LDX2-50 |
50A |
22kW |
|
LDX2-65 |
65A |
30kW |
|
LDX2-80 |
80A |
37kW |
|
LDX2-95 |
95A |
45kW |
Auxiliary Circuit Parameters
|
Use Category |
Rated Voltage |
Rated Thermal Current |
Rated Operating Current |
Control Capacity |
|
AC-15 |
380V |
10A |
0.95A |
3600VA making / 360VA breaking |
|
DC-13 |
220V |
10A |
0.15A |
33W making / 33W breaking |
Working Conditions
|
Item |
Specification |
|
Ambient air temperature |
-5°C to +40°C |
|
24-hour average temperature |
<= +35°C |
|
Altitude |
<= 2000m |
|
Relative humidity |
<=50% at +40°C; higher humidity allowed at lower temperature |
|
Wettest month condition |
Average minimum temperature <= +25°C; average maximum relative humidity <=90% |
|
Installation category |
III |
|
Installation inclination |
Mounting surface inclination <= +/-5 degrees from vertical |
|
Shock and vibration |
Use in locations without obvious impact, shock, or vibration |
Structure and Installation Advantages
- Three main poles are suitable for standard three-phase motor control circuits.
- Optional auxiliary contact blocks, delay heads, mechanical interlock mechanisms, and thermal relay accessories can be combined into derived control products.
- Models below 32A usually provide one pair of auxiliary contacts; 40A and above can provide auxiliary contact combinations according to configuration.
- Except for screw mounting, the series supports 35mm rail installation and selected larger sizes can also use 75mm rail installation.
- Control coil terminal markings A1 and A2 help simplify wiring identification.
- Compact structure supports space-saving design in distribution cabinets and machine control panels.
Typical Applications
This three-pole contactor series is suited to control systems that need reliable AC motor switching, compact installation, and flexible auxiliary control options.
- Three-phase motor control cabinets and electromagnetic starters
- Pump, fan, compressor, and conveyor control circuits
- HVAC and building automation panels
- Industrial machinery control systems
- Distribution boards and automation cabinets
- Frequent start-stop motor applications
- Control panels using contactor plus overload relay combinations
Installation, Use, and Ordering Notes
- Before installation, verify that coil voltage, rated current, and operating frequency match the power supply and load.
- Tighten terminal screws correctly and check the wiring before energizing the main contacts.
- Avoid dropping washers, wire ends, and other foreign objects into the contactor during installation.
- If abnormal noise occurs during operation, clean the pole surface or check for foreign matter.
- Regularly inspect product parts during use; replace damaged components promptly.
- When ordering, specify contactor model, coil rated voltage and frequency, quantity, and whether auxiliary contacts or standard rail accessories are required.