Product Overview
The LDB9-63 series miniature circuit breaker is designed for dependable overload and short-circuit protection in low-voltage AC distribution systems. It supports residential buildings, commercial facilities, industrial panels, lighting circuits, socket circuits, and small motor control applications.
With B, C, and D tripping characteristic options, clear contact position indication, durable front marking, and energy limiting class 3 performance, this breaker helps improve electrical safety while keeping panel installation and daily maintenance efficient.
Key Features
- Complete circuit protection: Designed for overload and short-circuit protection in AC low-voltage distribution systems.
- Flexible current range: Rated current options include 2A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, and 63A.
- Multiple pole options: Available in 1P, 1P+N, 2P, 3P, 3P+N, and 4P configurations.
- B, C, and D trip curves: Supports protection for resistive loads, regular loads, small motors, and high-inrush circuits.
- Reliable breaking capacity: Rated short-circuit breaking capacity is 6kA.
- Clear status indication: A visible indication window below the handle shows ON/OFF contact position.
- Durable identification: Front printing is designed for long-term readability and easier maintenance.
- Enhanced safety design: Energy limiting class 3 and restricted ionized gas emission with 45mm grid distance.
Main Technical Specifications
|
Item |
Specification |
|
b |
LDB9-63 |
|
Product type |
Miniature circuit breaker |
|
Function |
Overload and short-circuit protection |
|
Standards |
IEC60898-1 / GB/T10963.1 |
|
Approvals |
CE, CB, SAA |
|
Rated current, In |
2A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
|
Rated voltage, Ue |
230/240V for 1P and 1P+N; 400/415V for 2P-4P and 3P+N |
|
Rated frequency |
50/60Hz |
|
Rated insulation voltage |
500V |
|
Rated impulse withstand voltage |
4kV |
|
Rated short-circuit breaking capacity, Icn |
6kA |
|
Protection level |
IP20 |
|
Electrical life |
10,000 operations |
|
Mechanical life |
20,000 operations |
|
Fire resistance |
V0 grade |
|
Energy limiting class |
3 |
|
Mounting position |
Any position |
|
Conductor cross-section |
Solid conductor: 1-35mm2; stranded conductor: 1-25mm2 |
|
Maximum terminal tightening torque |
3.5N*m |
|
Ambient temperature |
-25°C to +45°C, maximum humidity 95% |
|
Storage temperature |
-40°C to +75°C |
|
Installation altitude |
Not more than 2000m |
Tripping Characteristics
|
Curve |
Instantaneous Trip Range |
Recommended Application |
|
B |
3In to 5In |
Resistive loads such as electric heaters, water heaters, and electric stoves |
|
C |
5In to 10In |
General circuits such as lighting, power sockets, and small motors |
|
D |
10In to 20In |
Circuits with high instantaneous inrush current, such as large motor loads |
Thermal Release Reference
|
Test Current |
Tripping Time |
|
1.13In |
t >= 1h for In <= 63A |
|
1.45In |
t < 1h for In <= 63A |
|
2.55In |
1s < t < 60s for In <= 32A; 1s < t < 120s for In > 32A |
Recommended Applications
This breaker is suitable for distribution circuits that need compact protection, clear switching status, and reliable tripping performance.
- Residential distribution boards
- Commercial building lighting and socket circuits
- Small motor circuits
- Industrial control and distribution panels
- Infrastructure and energy distribution systems
- Circuits requiring B, C, or D curve protection coordination
Installation and Selection Notes
- Select the rated current according to load current, cable size, and protection coordination.
- Choose the tripping curve according to load type and expected inrush current.
- Confirm pole configuration and rated voltage before ordering.
- Use the specified terminal tightening torque to ensure safe conductor connection.
- Install the product in a suitable electrical enclosure; the protection level is IP20.
- Installation and maintenance should be performed by qualified electrical personnel after power isolation.
Model Selection Notes
When selecting an LDB9-63 breaker, confirm rated current, pole number, tripping curve, breaking capacity, operating voltage, installation environment, and order quantity. For projects with mixed loads, use separate circuit protection selections for resistive, general, and high-inrush circuits.
Request a Quote
Send us your rated current, voltage, pole configuration, tripping curve, breaking capacity requirement, and application scenario. Our team can help select the correct LDB9-63 configuration for safe and efficient low-voltage circuit protection.
Hot Tags: high performance mcb, China high performance mcb manufacturers, suppliers, factory, 1PN Breaker, circuit breakers, High Performance MCB, mcb